Specifications
| Model | IC180 |
|---|---|
| Size (H x W x D) | 151 x 165 x87 cm |
| Weight | Dry: 350kg/ Operational: 400kg |
| Coolant | Synthetic Oil |
| Maximum cooling capacity | 180kW @ flow rate=300LPM, △T=24°C* |
| Pump | Dual redundant inverter pump (1+1) |
| Operating flow rate | 400LPM @ △P< 15mH2O |
| LCD Monitor | 10“ LCD Touch panel |
| Water temperature in primary loop | 7~25°C |
| Water temperature in 2nd loop | 18~40°C |
| Coolant temperature range | Inlet 35~50℃, outlet 45~55℃ |
| Pipework connection | Stainless steel flange, ISO7241-B quick connector |
| Noise | < 55 dBA ( in 3m) |
| Dew point control | YES |
| Web communication function | TCP/IP |
| Modbus communication function | RS485 RTU |
| Power consumption | 8kW |
| Power Specifications | 380~400V, 50/60 Hz three-phase three-wire AC, 20A pluggable dual-circuit power supply |